Cooling Capacity 20, 150 kW; Connections 3/4'' FNPT, 2” Copper Flange; Temperature Stability ±0.5, ±1.0 °C; Facility Water Temperature +10 to +35 °C, +4 to +12 °C; CE Certified
Lytron’s LCS series of liquid-to-liquid cooling systems is an excellent solution for high heat-load or high ambient temperature applications where chilled facility water is available. The LCS series offers precise temperature control of process water and transfers the waste heat to your facility water via a liquid-to-liquid heat exchanger.
With 20 kW of cooling, Lytron’s LCS20 provides over three times the capacity of a comparably-sized recirculating chiller, providing a great solution for high heat loads where space is at a premium.
Designed for data center cooling, Lytron’s LCS50 is a 150 kW liquid-to-liquid cooling system that supplies precisely temperature-controlled coolant to your liquid cooled racks and transfers the waste heat to facility water.
Key Features:
- Large Cooling Capacity (20, 150 kW) in a Compact Package
- Tight Temperature Control: ±0.5, ±1.0 °C (Despite Fluctuations in the Facility Water Temperature and Flow Rate)
- Contamination-free: Process Cooling Loop Isolated from the Facility Water
- Reliable, Quiet and Energy-efficient
- Fluid Connections: ¾” FNPT (LCS20), 2” Copper Flange (LCS50)
- Coolant Temperature Range: +10 to +60 °C (LCS20), +5 to +35 °C (LCS50)
- Facility Water Temperature Range: +10 to +35 °C (LCS20), +4 to +12 °C (LCS50)
- Facility Flow Rate: 8 to 38 l/min (LCS20), 95 to 379 l/min (LCS50)
- Maximum Facility Pressure: 7 bar
- Ambient Temperature Range: +5 to +40 °C
Applications: Electronics Cooling; High Heat-load or High Ambient Temperature Applications Where Chilled Facility Water is Available